How a feed-through terminal works

A feed-through terminal gives a wire entering from one side a connection point to the wire leaving from the other. In a control cabinet, a row of these blocks can provide an orderly interface between field wiring and panel wiring.

  • Wire entries guide the prepared conductors into the terminal.
  • Screw clamps hold the conductors against the internal current path.
  • Rail mounting foot secures the terminal to a compatible DIN rail.
  • End accessories serve different purposes. An end bracket restrains the row on the rail. An end plate closes an exposed side where the terminal design requires one.
Illustrative exploded view of a screw-clamp DIN rail terminal
Illustration of the insulating housing, screws, clamp cages and conductor link.

Inside a screw terminal

Insulating housing

Separates the conducting parts from adjacent terminals.

Conductive link and clamps

The link provides the current path. The clamps secure the conductor at each end.

Clamping screws

Apply pressure to the termination. Check the model’s material, plating and torque requirements when specifying a part.

Where terminal strips fit

Illustrated control cabinet with a row of DIN rail terminal blocks
Illustrative control cabinet layout with terminal blocks, wiring duct and panel devices.

Machine control cabinet

Bring field wiring into the panel at a labeled row.

Machine wiring→Terminal strip→Panel wiring

Sensor junction box

Provide a service point between outgoing field devices and the incoming cable.

Field sensors→Terminal strip→Multicore cable

Control-circuit wiring

Organize terminals by circuit and identify each group with markers.

Control circuit→Marked terminals→Outgoing wiring

Illustrative layouts. Select each terminal and accessory for the actual circuit.

Mount, wire and inspect

Have a qualified person isolate the circuit and verify absence of voltage before working on the panel.

Fit the terminal to the rail

DIN rail mounting and release
  1. Hook the foot onto the rail. With one foot engaged, pivot the block toward the opposite rail edge.
  2. Release the retaining foot. Start with the block still on the rail. Once the foot clears the rail edge, pivot the block away.
Photo-based illustration.
Hook the foot onto the rail.
Hook the foot onto the rail. With one foot engaged, pivot the block toward the opposite rail edge.
Release the retaining foot.
Release the retaining foot. Start with the block still on the rail. Once the foot clears the rail edge, pivot the block away.

Prepare, insert and clamp the wire

Screw-clamp wiring sequence
  1. Prepare the conductor. Strip to the specified length and use a compatible ferrule where required.
  2. Open the clamp. Use the screwdriver from the top of the same side that will receive the wire.
  3. Insert through the side entry. Seat the conductor fully inside the open clamp.
  4. Tighten the screw. Use the specified torque and verify that the conductor is secure.
Photo-based illustration.
Prepare the conductor.
Prepare the conductor. Strip to the specified length and use a compatible ferrule where required.
Open the clamp.
Open the clamp. Use the screwdriver from the top of the same side that will receive the wire.
Insert through the side entry.
Insert through the side entry. Seat the conductor fully inside the open clamp.
Tighten the screw.
Tighten the screw. Use the specified torque and verify that the conductor is secure.

Accessories on an assembled row

Illustrated bridge, end plate and end bracket for a DIN rail terminal row
Left: bridge. Center: end plate. Right: end bracket.

What to check before selecting a model

1. Match the conductor to the clamp

Start with the actual conductor cross-section and construction. A terminal’s nominal cross-section is a catalog designation. The allowable range can differ for solid, stranded and ferruled conductors, so check the range for the exact termination method.

2. Check rail fit and cabinet space

Confirm the rail profile, terminal width and space for wire bends, markings and accessories. If you need to join adjacent circuits using a bridge, confirm the terminal pitch and compatible bridge part before laying out the row.

3. Verify the electrical requirements

Compare the circuit’s required voltage and current with the rating for the exact terminal model and its application conditions. For a protective-earth connection, specify a dedicated PE terminal and follow the panel’s grounding design.

Example. PEVXI UK2.5B and UK3N both have a nominal conductor cross-section of 2.5 mm². When choosing between them, compare the conductor range, rail fit, terminal width and required accessories for your layout. PEVXI UK5N is listed at 4 mm² nominal.

Compare PEVXI UK models

All ten models below are single-level screw-clamp feed-through terminals. Product photos are identification views and are shown independently of physical scale.

Model UK1.5N UK2.5B UK3N
Product UK1.5N terminal block in gray UK2.5B terminal block in gray UK3N terminal block in gray
Nominal section 1.5 mm² 2.5 mm² 2.5 mm²
Colors GrayRedBlue GrayBlackRedBlueYellowGreen GrayBlackRedBlueYellowGreen
Model UK5N UK6N UK10N
Product UK5N terminal block in gray UK6N terminal block in gray UK10N terminal block in gray
Nominal section 4 mm² 6 mm² 10 mm²
Colors GrayBlackRedBlueYellowGreen GrayBlackRedBlueYellowGreen GrayBlackRedBlueYellowGreen
Model UK16N UK25N UK35N UK50N
Product UK16N terminal block in gray UK25N terminal block in gray UK35N terminal block in gray UK50N terminal block in gray
Nominal section 16 mm² 25 mm² 35 mm² 50 mm²
Colors GrayRedBlueYellowGreen Gray GrayBlue GrayBlue

UK2.5B colors in product photos

UK2.5B in gray
Gray · UK2.5B
UK2.5B in black
Black · UK2.5B
UK2.5B in red
Red · UK2.5B
UK2.5B in blue
Blue · UK2.5B
UK2.5B in yellow
Yellow · UK2.5B
UK2.5B in green
Green · UK2.5B

Blue options for larger sections

UK35N in blue
Blue · UK35N
UK50N in blue
Blue · UK50N

Color chips identify catalog options. Product photographs are shown where a matching color photo is available.

Before final selection, confirm the accepted conductor range, rail profile, terminal width, stripping length, tightening torque and electrical ratings for your exact model.

Browse the PEVXI UK series